Air Conditioning Calculator

Answer a few quick questions and we’ll size the right air conditioning system for your room — instant BTU, kW and recommended evaporator size.

Step 1 of 6Project details

Project details

Ventilation Calculator

Size room airflow and duct diameter per UK Part F guidance — instant L/s, m³/h, CFM and duct size.

Room & airflow

Design Airflow — Office

80.0 L/s

m³/h

288.0

CFM

169.5

Duct diameter

184 mm

Volume

48.0

Breakdown

Room volume
48.0 m³
Airflow (ACH method)
80.0 L/s (288.0 m³/h)
Airflow (per person, 10 L/s)
40.0 L/s
Duct area required
0.0267 m²
Design airflow
80.0 L/s

UK Part F — typical minimum extract rates

Kitchen
13 L/s
Utility
8 L/s
Bathroom
8 L/s
WC
6 L/s

Refrigerant Slider

Convert between saturation pressure and temperature for common HFC refrigerants. For field guidance only — use manufacturer P–T charts for commissioning.

-50 °C60 °C

R410A — saturation

8.35 bar(g)

Dew °C

5.00

Bubble °C

4.97

Glide K

0.03

Phase

dew

Properties — R410A

Class
HFC blend
Safety group
A1
GWP (AR4)
2,088
ODP
0
Oil
POE
Nominal glide
0.1 K
Boiling pt (1 atm)
-51.6 °C
Critical temp
71.36 °C

Saturation values are calculated from fitted curves and intended for guidance only. Use manufacturer P–T charts for commissioning and safety-critical work.

F-Gas & EN378 Safety Calculator

Check refrigerant concentration against EN378-1 practical and flammability limits, and get the matching UK F-Gas leak-check interval.

EN378 Design Check

Requires further investigation

Concentration vs EN378 limits

Calculated concentration
0.0600 kg/m³
EN378 practical limit (RCL)
0.0610 kg/m³
% of practical limit
98.4%
LFL (flammability)
0.307 kg/m³
% of LFL
19.5%
ATEL (toxicity)
0.3 kg/m³

UK F-Gas (Regulation 517/2014)

GWP (AR4, 100-yr)
675
Charge
3 kg
CO₂-equivalent
2.02 t CO₂e
Mandatory leak check
Not required (< 5 tCO₂e)

Indicative only. Verdict uses EN378-1 simplified rules: occupied spaces compared to the practical limit (50% triggers review), authorised-access areas compared to 0.5×LFL for flammable gases. Plant rooms and outdoor systems are subject to ventilation/detection requirements rather than concentration limits. For certification, undertake the full EN378 assessment.

F-Gas GWP & tCO₂e Calculator

Refrigerant → charge (kg) → GWP → tonnes CO₂e → the legal F-Gas leak-check frequency, with your next check date.

System 1

GWP (AR4)

2,088

Charge

5 kg

CO₂ equivalent

10.44 t

Legal leak-check frequency

Every 12 months

Band: 5 to under 50 tCO2e

  • • Records must be kept for 5 years (charge, checks, recovery, engineer details).
  • • AR5 GWP (reporting reference only): 1,924 — legal thresholds use AR4.

Based on the GB F-Gas Regulation (retained EU 517/2014) Articles 4 & 5 using AR4 GWP values. Hermetically sealed systems below 10 tCO₂e and labelled as such are exempt from leak checking. Indicative guidance only — confirm against current legislation.