Daikin Error Codes

Daikin splits (FTX/FTXM) and VRV display 2-character codes on the BRC controller or by indoor LED flashes.

A1

Indoor PCB defect

Cause:
Indoor main PCB failure
Action:
Power-cycle; replace indoor PCB if persists.

A3

Drain level abnormal

Cause:
Float switch tripped / drain pump failed
Action:
Clear drain, test pump and float.

A5

Indoor freeze-up / overheat protection

Cause:
Low airflow, dirty filter, low charge
Action:
Clean filter & coil, check fan, charge.

A6

Indoor fan motor fault

Cause:
Stalled or failed DC fan motor
Action:
Test motor and PCB feedback signal.

C4

Indoor liquid pipe thermistor (R2T) fault

Cause:
Open / short sensor
Action:
Replace liquid pipe sensor.

C5

Indoor gas pipe thermistor (R3T) fault

Cause:
Open / short sensor
Action:
Replace gas pipe sensor.

C9

Indoor suction air thermistor (R1T) fault

Cause:
Open / short sensor
Action:
Replace suction sensor.

E1

Outdoor PCB defect

Cause:
Outdoor main PCB failure
Action:
Replace outdoor PCB.

E3

High pressure switch activated

Cause:
Blocked condenser, overcharge, fan fault
Action:
Inspect condenser, fan, charge, EEV.

E4

Low pressure switch activated

Cause:
Undercharge, blocked filter drier
Action:
Leak test, check filter drier and EEV.

E5

Compressor motor lock / overload

Cause:
Locked rotor or compressor failure
Action:
Megger compressor, test inverter.

E6

Compressor startup failure

Cause:
Low DC bus, IPM, locked rotor
Action:
Check supply, inverter PCB, compressor.

E7

Outdoor fan motor fault

Cause:
Stalled / failed fan motor
Action:
Test fan motor and driver.

F3

Discharge pipe temperature too high

Cause:
Low charge, EEV stuck closed
Action:
Check charge, EEV, Td sensor.

H6

Position sensor fault (compressor)

Cause:
Inverter PCB or compressor fault
Action:
Replace inverter PCB.

L5

Compressor IPM overcurrent (instantaneous)

Cause:
Locked rotor, IPM short
Action:
Megger compressor, replace inverter.

U0

Refrigerant shortage

Cause:
Loss of refrigerant charge
Action:
Leak test and recharge to spec.

U2

Power supply voltage abnormal

Cause:
Low/high mains or DC bus drop
Action:
Measure supply, check rectifier / DC bus.

U4

Indoor ↔ outdoor transmission error

Cause:
F1/F2 wiring or PCB fault
Action:
Check F1/F2 polarity, length and PCBs.

UA

Indoor/outdoor mismatch

Cause:
Incompatible combination or too many units
Action:
Check pairing and quantity vs spec.

For field guidance only. Codes and procedures vary by model and firmware — always confirm with the Daikin service manual for the specific unit before carrying out a repair.