Toshiba Error Codes
Toshiba (RAS / SMMS / SHRM) shows alphanumeric check codes on the wired controller; outdoor PCB has 7-segment display.
F01
Indoor TCJ sensor (coil out) error
- Cause:
- Open / short TCJ sensor
- Action:
- Replace TCJ thermistor.
F02
Indoor TC2 sensor (coil) error
- Cause:
- Open / short TC2 sensor
- Action:
- Replace TC2 thermistor.
F03
Indoor TC1 sensor (coil in) error
- Cause:
- Open / short TC1 sensor
- Action:
- Replace TC1 thermistor.
F04
Outdoor TD1 (discharge) sensor error
- Cause:
- Open / short Td sensor
- Action:
- Replace TD1 sensor.
F06
Outdoor TE / TS sensor error
- Cause:
- Open / short outdoor coil/suction sensor
- Action:
- Replace affected sensor.
F07
Outdoor TL (liquid) sensor error
- Cause:
- Open / short TL sensor
- Action:
- Replace TL sensor.
F08
Outdoor TO (ambient) sensor error
- Cause:
- Open / short OAT sensor
- Action:
- Replace TO sensor.
F10
Indoor TA (return air) sensor error
- Cause:
- Open / short TA sensor
- Action:
- Replace TA sensor.
F29
Indoor PCB other error
- Cause:
- Indoor PCB hardware fault
- Action:
- Replace indoor PCB.
H01
Compressor break-down (overcurrent)
- Cause:
- IPM overcurrent / locked rotor
- Action:
- Megger compressor, replace inverter.
H02
Compressor locked
- Cause:
- Mechanical seizure or wiring
- Action:
- Test compressor windings and replace if seized.
H03
Current detection circuit error
- Cause:
- CT or PCB fault
- Action:
- Replace outdoor PCB.
L03
Duplicated indoor header unit
- Cause:
- Two indoor headers set on group
- Action:
- Re-address indoor units.
L08
Indoor group/address not set
- Cause:
- Missing address after install
- Action:
- Run auto-address.
L29
Number of outdoor units error
- Cause:
- OD count mismatch
- Action:
- Check OD DIP and wiring.
P03
Discharge temperature TD1 too high
- Cause:
- Low charge, EEV closed
- Action:
- Check charge, EEV, Td sensor.
P04
High-pressure switch trip
- Cause:
- Blocked condenser, overcharge
- Action:
- Clean condenser, check fan and charge.
P05
Reverse phase / open phase (3-ph)
- Cause:
- Wrong phase rotation or missing phase
- Action:
- Swap any two phases or fix supply.
P07
Heat-sink (IGBT) overheat
- Cause:
- Inverter heatsink too hot
- Action:
- Clean heatsink, check fan and paste.
P22
Outdoor fan motor error
- Cause:
- Stalled / failed fan
- Action:
- Test fan and driver.
P26
Compressor inverter IPM short-circuit
- Cause:
- IPM fault
- Action:
- Replace inverter PCB.
P29
Compressor position detection error
- Cause:
- Inverter PCB or compressor wiring
- Action:
- Check leads, replace inverter if needed.
For field guidance only. Codes and procedures vary by model and firmware — always confirm with the Toshiba service manual for the specific unit before carrying out a repair.