Samsung (AR/AJ/DVM S) shows E1xx / E2xx / E4xx codes on the wired controller or wireless display.

E101

Indoor ↔ outdoor communication error

Cause:
F3/F4 comms cable open or noise
Action:
Check F3/F4 wiring, screen earth, replace PCB if needed.

E121

Indoor room temperature sensor (Eva-In) error

Cause:
Short / open sensor
Action:
Measure thermistor and replace.

E122

Indoor coil (Eva-In) sensor error

Cause:
Short / open pipe-in sensor
Action:
Replace sensor.

E123

Indoor coil (Eva-Out) sensor error

Cause:
Short / open pipe-out sensor
Action:
Replace sensor.

E135

Indoor coil mid sensor error

Cause:
Short / open mid pipe sensor
Action:
Replace sensor.

E154

Indoor fan motor (BLDC) feedback error

Cause:
Stalled fan or PCB driver fault
Action:
Spin fan by hand, test motor windings, replace motor or PCB.

E163

Mixed indoor model code error

Cause:
Mismatched indoor units on network
Action:
Verify compatible models on the same outdoor.

E201

No communication between outdoor and indoor

Cause:
Open F3/F4 between OD↔ID or no power on ID
Action:
Check ID power and interconnect.

E202

Communication error after a period

Cause:
Intermittent interconnect or noise
Action:
Re-terminate F3/F4, check shielding/earth.

E221

Outdoor air sensor error

Cause:
Short / open OAT sensor
Action:
Replace OAT thermistor.

E237

Outdoor heat exchanger sensor error

Cause:
Short / open OD coil sensor
Action:
Replace sensor.

E251

Discharge temperature sensor 1 error

Cause:
Open / short Td sensor
Action:
Replace Td sensor.

E416

Compressor discharge temperature high

Cause:
Low charge, restricted flow, EEV fault
Action:
Check charge, EEV, condenser airflow.

E422

EEV leakage / closed-EEV during off cycle

Cause:
EEV not seating
Action:
Test EEV coil and body, replace if stuck.

E440

Heating operation blocked (outdoor too high)

Cause:
OAT outside heating envelope
Action:
Normal protection — wait for ambient drop.

E458

Outdoor fan 1 error

Cause:
Stalled / open fan motor
Action:
Check fan, capacitor (if AC) or PCB driver.

E464

IPM (inverter power module) overcurrent

Cause:
Compressor overload or IPM failure
Action:
Megger compressor, replace inverter PCB.