LG (Multi V, Multi Split, single splits) shows CHxx codes on wired controllers; wireless units flash indoor LEDs.

CH01

Indoor air thermistor open/short

Cause:
Faulty return air sensor
Action:
Replace indoor air thermistor.

CH02

Indoor inlet pipe thermistor open/short

Cause:
Faulty inlet pipe sensor
Action:
Replace inlet pipe thermistor.

CH03

Wired remote controller communication error

Cause:
RC cable / PCB fault
Action:
Check RC cable polarity and replace if needed.

CH04

Float switch / drain pump fault

Cause:
Drain trip
Action:
Clear drain, test pump and float.

CH05

Indoor ↔ outdoor communication error

Cause:
Open interconnect or PCB fault
Action:
Verify F1/F2 wiring and 24 V comms.

CH06

Indoor outlet pipe thermistor open/short

Cause:
Faulty outlet pipe sensor
Action:
Replace outlet pipe thermistor.

CH07

Indoor units mode mismatch

Cause:
Cooling/heating conflict on multi system
Action:
Set all indoor units to same mode.

CH09

Indoor EEPROM error

Cause:
Indoor PCB EEPROM corrupt
Action:
Replace indoor PCB.

CH10

Indoor fan motor (BLDC) lock

Cause:
Stalled / failed fan motor
Action:
Test fan and feedback signal.

CH21

Inverter compressor IPM fault / overcurrent

Cause:
Locked rotor, IPM failure
Action:
Megger compressor, replace inverter PCB.

CH22

Compressor CT (high current) trip

Cause:
Compressor overload
Action:
Check charge and condenser airflow.

CH23

DC link low voltage

Cause:
Mains supply or rectifier fault
Action:
Measure supply and DC bus.

CH26

Compressor position sensing error

Cause:
Inverter PCB or compressor wiring
Action:
Re-seat compressor leads, test inverter.

CH27

PSC / PFC circuit error

Cause:
Inverter PFC failure
Action:
Replace inverter PCB.

CH32

Discharge pipe temperature high

Cause:
Low charge, EEV stuck
Action:
Check charge, EEV, Td sensor.

CH41

Compressor discharge sensor (D-pipe) fault

Cause:
Open / short Td sensor
Action:
Replace Td sensor.

CH44

Outdoor air thermistor fault

Cause:
Open / short OAT sensor
Action:
Replace OAT thermistor.

CH45

Outdoor coil (mid) thermistor fault

Cause:
Open / short coil sensor
Action:
Replace coil thermistor.

CH53

Communication error (indoor → outdoor)

Cause:
Comms cable issue
Action:
Check F1/F2 wiring.

CH60

Outdoor EEPROM error

Cause:
Outdoor PCB EEPROM fault
Action:
Replace outdoor PCB.

For field guidance only. Codes and procedures vary by model and firmware — always confirm with the LG service manual for the specific unit before carrying out a repair.