Fujitsu (ASYG/AOYG, AirStage VRF) flashes Operation + Timer LEDs; wired controllers show E:EE codes.

E:EE 11.1

Indoor unit communication error

Cause:
Indoor ↔ outdoor comms lost
Action:
Check 1-2-3 interconnect and PCB.

E:EE 12.1

Indoor unit address setting error

Cause:
Duplicate / unset address
Action:
Re-set DIP switches or auto address.

E:EE 13.1

Wired remote controller communication error

Cause:
RC cable fault
Action:
Check 2-core RC cable polarity.

E:EE 14.1

Network communication error

Cause:
VRF network fault
Action:
Inspect outdoor-outdoor comms and terminator.

E:EE 21.1

Indoor return air thermistor (Ta) error

Cause:
Open / short Ta sensor
Action:
Replace return air thermistor.

E:EE 22.1

Indoor heat exchanger pipe thermistor error

Cause:
Open / short coil sensor
Action:
Replace coil thermistor.

E:EE 31.1

Discharge pipe sensor error

Cause:
Open / short Td sensor
Action:
Replace discharge sensor.

E:EE 32.1

Compressor temperature sensor error

Cause:
Open / short sensor
Action:
Replace compressor temperature sensor.

E:EE 33.1

High-pressure switch activated

Cause:
Blocked condenser, overcharge
Action:
Clean condenser, check charge and fan.

E:EE 41.1

Discharge pipe temperature trouble

Cause:
Low charge, EEV closed
Action:
Check charge, EEV and Td sensor.

E:EE 42.1

Compressor temperature trouble

Cause:
Compressor overheating
Action:
Check oil return, charge, EEV.

E:EE 43.1

High-pressure trouble

Cause:
HP trip
Action:
Inspect condenser, fan and charge.

E:EE 44.1

Low-pressure trouble

Cause:
LP trip
Action:
Leak test, check filter drier.

E:EE 51.1

Indoor fan motor abnormal

Cause:
Stalled / failed indoor fan
Action:
Test motor windings and PCB feedback.

E:EE 53.1

Drain pump abnormal

Cause:
Float trip / pump fault
Action:
Clear drain and test pump.

E:EE 61.1

Outdoor PCB error

Cause:
Outdoor main PCB fault
Action:
Power-cycle, replace if persists.

E:EE 96.1

Inverter compressor IPM error

Cause:
Overcurrent / IPM failure
Action:
Megger compressor, replace inverter PCB.

For field guidance only. Codes and procedures vary by model and firmware — always confirm with the Fujitsu service manual for the specific unit before carrying out a repair.